Home › Equipment › Comparison

Equipment comparison

Specifications, installed-cost drivers and energy performance across eight commercial mechanical equipment types.

Capacity ranges are typical published commercial product ranges for familiarity, not limits; efficiency benchmarks cite standard minimums at stated rating conditions, which change as DOE and ASHRAE editions update.

No universal installed-price range is verified here. Obtain dated, local quotations for the same capacity, duty, redundancy and complete installed scope. Equipment-only prices are not installed costs; dollar-per-ton comparisons are not interchangeable across heating, cooling and heat-rejection equipment.

Ratings use different tests and system boundaries. Compare like-for-like certified equipment at stated conditions, then model annual loads, climate, ventilation, tariffs and all auxiliaries. No equipment type is universally the most efficient or lowest cost.

Side-by-side equipment comparison

Commercial mechanical equipment: specifications, costs and energy efficiency
ComparisonChillersBoilersVRFWater-source heat pumpsSplit systemsPackaged unitsRooftop unitsCooling towers
Building roleCentral chilled-water or process cooling. Heat-recovery models can also supply useful heat.Heating hot water or steam for building or process loads; not a cooling system.Zoned refrigerant heating and cooling; suitable heat-recovery configurations can serve simultaneous heating/cooling loads.Local zone heat pumps exchanging heat with a shared building water loop or a designed ground/water-source loop.Distributed DX cooling or heat-pump heating/cooling. Cooling-only splits require a separate heat source when heating is needed.Self-contained air conditioning with selected heating options, serving a defined area. Heating capability depends on the model.Usually roof-mounted packaged DX equipment with gas, electric or heat-pump heating options.Reject heat from condenser water or a shared-loop system. Not a standalone refrigeration machine or occupied-space cooling system.
Specification checklistCooling capacity (tons or kW); supply/return fluid temperatures; flow and pressure drop; condenser conditions; refrigerant; compressor type; electrical input and sound.Fuel or electric input; useful output (Btu/h or kW); hot-water temperatures/flow or steam pressure/output; turndown; venting; water quality and pressure rating.Outdoor and indoor capacities; connected-capacity ratio; refrigerant/charge; pipe-length and elevation limits; heating capacity at design outdoor temperature; indoor-unit configuration.Cooling/heating capacity; entering-water and air conditions; required loop flow and pressure drop; fan/external static pressure; electrical input; acoustic requirements.Matched indoor/outdoor capacity; refrigerant; piping limits; cooling and low-ambient heating capacity; airflow/static pressure; electrical input.Cooling capacity; heating fuel/type and output; airflow/static pressure; outdoor-air/economizer capability; filtration; electrical service; footprint and sound.Cooling/heating capacity; airflow/static pressure; economizer/outdoor air; roof-curb dimensions; weight/structural loads; clearances; electrical and fuel connections.Heat-rejection duty; water flow; entering/leaving water temperatures; design wet-bulb; approach/range; fan power; sound; drift and water-quality requirements.
Typical capacity rangeAir-cooled scroll/screw: roughly 10–500 tons. Water-cooled screw: roughly 100–1,000 tons. Water-cooled centrifugal: roughly 150 tons to over 3,000 tons per machine; plants combine machines.Commercial packaged boilers: 300,000 Btu/h to several million Btu/h per boiler (federal commercial category starts at 300,000 Btu/h). Plants often stage several modular units.Outdoor modules roughly 6–30 tons each; modules combine into systems of about 40+ tons. Indoor units from about 0.5 ton (wall/cassette) to ducted units of several tons.Console and small horizontal units about 0.5–1.5 tons; typical zone units 1–5 tons; large vertical units up to about 25 tons.Ductless mini-splits about 0.75–3 tons per indoor unit; commercial ducted splits about 1.5–25 tons, with larger custom split DX available.Light-commercial packaged units about 3–25 tons; large packaged and indoor self-contained units about 20–150+ tons.Light-commercial RTUs about 3–25 tons; large RTUs about 25–150 tons, with some custom lines above 200 tons.Factory-assembled cells roughly 50–1,500 nominal tons each; field-erected towers serve plants of thousands of tons.
Distribution & supporting equipmentChilled-water pumps, piping and air-handler/fan-coil or process heat exchangers.Hot-water pumps/piping or steam supply and condensate return. Domestic hot water requires appropriate separate heat exchange.Refrigerant piping, indoor units and, where applicable, branch/heat-recovery devices. Designed ventilation and humidity control remain separate needs.Shared-loop piping/pumps plus zone air distribution. Building loops may need supplemental heat and heat rejection; ground-coupled systems differ.Indoor coil/air handler plus outdoor unit, refrigerant lines and ductwork or ductless indoor delivery.Major components in one assembly; ducts connect equipment to occupied areas. Location can be ground, indoor or roof depending on design.Roof curb and supply/return duct connections; outdoor-air intake and controls within the selected configuration.Heat-rejection loop, pumps, piping, makeup water and treatment. Closed-circuit fluid coolers keep process fluid inside a coil and differ from open towers.
Installed-cost scopeChiller, rigging, electrical infrastructure, piping, pumps, insulation and controls. Water-cooled plants also need condenser-water infrastructure and heat rejection.Boiler, plant space, fuel/electrical service, combustion air, venting, pumps and piping. Condensing units need compatible flue and condensate management.Outdoor/indoor units, refrigerant distribution, branch devices, controls, electrical work and ventilation. Routing, access and refrigerant safety can materially affect scope.Zone units, loop piping/pumps, controls and ventilation. Include boiler/tower/fluid cooler or ground-loop scope where required.Matched indoor/outdoor equipment, line sets, electrical work, condensate and ducts where used. Include ventilation and any separate heating source.Equipment, foundation/support, ducts, electrical/fuel services, condensate, ventilation controls and access. Existing-duct compatibility affects replacements.Unit, crane/rigging, curb adaptation, structural/roofing work, ducts and utility connections. Access, roof condition and occupied-space constraints affect cost.Tower, support/rigging, condenser-water piping/pumps, electrical controls, makeup/blowdown and treatment equipment. Include access and water-management provisions.
Operating-cost driversCompressor electricity, pumping, fans and maintenance. Water-cooled plants add tower water, treatment and blowdown costs.Fuel/electricity, pumping, standby/distribution losses, maintenance and water treatment. Steam systems add condensate and trap-management considerations.Compressor and indoor-fan electricity, ventilation energy, service and refrigerant-circuit maintenance.Zone compressors/fans, loop pumps, supplemental heat and heat rejection; water treatment and maintenance where applicable.Compressor/fan electricity, auxiliary heating where applicable, filters, coil cleaning and service.Cooling/fan electricity, selected heating energy, ventilation loads, filters, coil cleaning and maintenance.Cooling/fan electricity, selected heating energy, ventilation loads and weather-exposed equipment maintenance.Fan/pump electricity, makeup water, sewer/blowdown charges, chemicals, cleaning and water-management labor.
Energy-efficiency metricsElectric chillers: full-load kW/ton or COP; IPLV/NPLV for defined part-load rating conditions. Lower kW/ton is better at the same conditions; higher COP is better.Fuel-fired commercial boilers: thermal efficiency or combustion efficiency, as applicable to the rating. These are different measures; identify the test basis and fuel.Cooling EER/IEER and heating COP, as applicable to the certified product class and rating standard. Check system combination, capacity class and test conditions.Cooling EER or the applicable seasonal cooling metric, and heating COP, under the relevant test procedure and entering-water/air conditions. Unit ratings are not whole-loop performance.SEER2/EER2/HSPF2 for applicable small unitary classes; EER/IEER and heating COP for applicable commercial classes. Identify the matched combination and standard.EER/IEER for applicable commercial cooling classes; applicable heating COP or fuel-heating efficiency. Small unitary classes may use seasonal metrics instead.EER/IEER for applicable commercial cooling classes; heating COP for heat-pump versions or applicable fuel-heating efficiency. Rating depends on the product class.Thermal heat-rejection performance at stated flow, wet-bulb and water temperatures; fan power and water use. Chiller kW/ton and cooling COP do not directly describe tower performance.
Efficiency benchmarksASHRAE 90.1-2019 Path A examples: air-cooled under 150 tons, minimum 10.1 EER full load / 13.7 IPLV; water-cooled centrifugal 300–400 tons, maximum 0.560 kW/ton full load / 0.520 IPLV. Magnetic-bearing and VFD centrifugal machines often rate well below the IPLV minimum at part load.Rated as thermal or combustion efficiency. Non-condensing gas hot-water boilers typically rate in the low-to-mid 80s percent thermal efficiency; condensing boilers commonly 90%+ when return water is cool enough to condense (roughly below 130°F). Verify the current DOE minimum for the size and fuel.Rated by AHRI 1230 in EER/IEER (cooling) and COP (heating). Certified commercial systems commonly list IEER in the high teens to upper 20s; check the AHRI directory for the exact matched combination.ASHRAE 90.1-2019 water-to-air, water-loop: 17,000–135,000 Btu/h minimum 13.0 EER cooling at 86°F entering water and 4.3 COP heating at 68°F. Ground-loop units are rated at different water conditions.Under 65,000 Btu/h single-phase: SEER2/HSPF2 under DOE residential rules. 65,000 Btu/h and above: commercial IEER under AHRI 340/360 (federal minimum around 14.8 IEER for 65,000–135,000 Btu/h air conditioners with electric or no heat).Air-cooled units 65,000 Btu/h and above rated in IEER under AHRI 340/360 (federal minimum around 14.8 IEER for 65,000–135,000 Btu/h with electric or no heat). Water-cooled self-contained units rated in EER/IEER at condenser-water conditions.Same commercial unitary metrics as packaged units: IEER for cooling and COP for heat-pump heating. High-efficiency variable-speed RTUs commonly rate several IEER points above the federal minimum.ASHRAE 90.1 rates tower fan efficiency in gpm per fan horsepower at standard conditions: open-circuit axial-fan towers minimum 40.2 gpm/hp; centrifugal-fan towers 20.0 gpm/hp. CTI certification confirms thermal capacity.
Real-world performanceCompare at the same temperatures, flow and load. Chiller-only ratings exclude much of the plant; evaluate pumps and heat rejection. Absorption needs separate thermal-input analysis.Condensing performance depends on sufficiently low return-water temperatures and operating conditions. Rated efficiency does not include all distribution and standby losses.Part-load operation and heat recovery can help under suitable loads. Piping, ambient temperature, defrost and simultaneous load balance affect actual performance.Shared-loop heat transfer can offset simultaneous heating/cooling loads. Loop temperature, pump energy and supplemental plant operation determine system results.Do not compare SEER2 directly with IEER. Duct losses, airflow, climate, defrost and auxiliary heat affect operating costs.Fan power, economizer operation, outdoor-air loads, controls and duct losses matter beyond the rated cooling value.Economizers can reduce mechanical cooling when conditions permit. Climate, humidity, sensors, fan control and commissioning govern benefit.Lower condenser-water temperatures may help a chiller, within its limits; optimize the combined plant rather than tower fan power alone.
Selection caveatWater-cooled and air-cooled arrangements have different water, space, sound and service requirements.Fuel type, heating-water versus steam duty, venting, redundancy and existing emitters govern selection.Heat-pump and heat-recovery VRF are not identical. Check refrigerant safety, low-ambient performance, service expertise and outdoor-air strategy.A water-source heat pump loop is not automatically a chilled-water system. Boiler/tower loops and ground-coupled loops are different designs.Split describes separated components, not a universal capacity or efficiency level. Ductless splits are not necessarily VRF.Packaged is an assembly description. It includes many RTUs; do not count packaged equipment and RTUs as universally separate alternatives.An RTU is commonly a packaged unit. Roof installation does not establish an efficiency ranking or guarantee suitable ventilation.Compare heat-rejection duty, not chiller evaporator tons. Evaporative towers and dry coolers have different water and temperature limitations.

Compare complete systems

Rooftop units commonly belong to the packaged-unit category. Boilers provide heat; cooling towers reject heat; neither is a standalone replacement for a cooling system.

Request capacity at design conditions, certified ratings, installed scope, annual energy modeling, maintenance and replacement allowances before comparing proposals.

Chillers guide

Boilers guide

VRF guide

Water-source heat pumps guide

Split systems guide

Packaged units guide

Rooftop units guide

Cooling towers guide

Technical references

Educational comparison, not a project estimate or equipment selection. Sources checked October 22, 2026; no affiliation or endorsement is implied.

DOE: commercial HVAC equipment and systems — Chillers, splits, packaged equipment and rooftop applications

Trane: VRF system types — Heat-pump versus heat-recovery VRF

Trane: water-source heat-pump system — Shared-loop heat transfer and supplemental heating / heat rejection

EPA WaterSense: cooling towers — Evaporative heat rejection and tower water management

DOE: purchasing energy-efficient electric chillers — Relevant full- and part-load performance comparisons

DOE FEMP: energy-efficient boilers — Fuel, capacity and thermal-efficiency distinctions; federal acquisition guidance, not a universal private-project mandate

AHRI 340/360: commercial unitary ratings — Rating scope for covered commercial packaged and split equipment; verify the currently applicable test procedure

AHRI: VRF certification program — VRF cooling EER/IEER and heating COP; a listed standard does not establish certification for every model

DOE: water-source heat-pump test procedure — Category-specific rating conditions and seasonal cooling metric

DOE FEMP: heating and cooling efficiency categories — Seasonal versus commercial rating metrics and capacity bands; federal purchasing requirements are not universal code requirements

CTI: thermal certification — Conformity with published thermal ratings, not a standalone electrical-efficiency ranking

Commercial mechanical careers and hiring

Equipment knowledge supports service, project delivery and controls careers. Gulfstream recruits for commercial mechanical contractors; directory references do not identify clients or project assignments.

Search mechanical jobs · Candidate application · Hire mechanical project managers · Related career guide

Featured hiring & salary guides

  • HVAC Service Manager Salary by Metro (2026)
  • Mechanical Superintendent Salary Guide (2026)
  • Controls / BAS Project Manager Salary Guide (2026)
  • How to Hire a Piping Superintendent (2026 Playbook)
  • Open Jobs
  • For Employers
  • For Candidates
  • Candidate Hub
  • 2026 Salary Guides
  • All Insights
  • Hiring & Salary Guides
  • Meet the Team
  • Regional Trade Reports
  • Local Unions Directory
  • Markets We Recruit In
  • About Gulfstream SP
  • Contact
  • Trust & Security
  • Privacy Policy